| Details: |
LC1-D series AC Contactor is suitable for using in the circuits up to the rated voltage 600V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently starting & controlling the AC moor. Combined with the auxiliary contact block, timer delay & machine-interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The Contactor is produced according to IEC60947-4, GB14048-4.
| Type | LC1-D09 | LC1-D12 | LC1-D18 | LC1-D25 | LC1-D32 | | Rated operational current (A) | AC-3 | 9 | 12 | 18 | 25 | 32 | | AC-1 | 3.5 | 5 | 7.7 | 8.5 | 12 | | AC3-capacity of phase 3 squirrel -cage motor ac3(kw) | 220V/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | | 380V/400V | 4 | 5.5 | 7.5 | 11 | 15 | | 415V | 4 | 5.5 | 9 | 11 | 15 | | 440V | 4 | 5.5 | 9 | 11 | 15 | | 500V | 5.5 | 7.5 | 10 | 15 | 18.5 | | 660V/692V | 5.5 | 7.5 | 10 | 15 | 18.5 | | Rated heat current (A) | 20 | 20 | 32 | 40 | 50 | | Electrical life | AC4 10 4 | 20 | 20-15 | 20-7 | 15-7 | 15-7 | | AC3 10 6 | 2 | 2 | 2 | 2 | 2 | | Mechanical life 10 6 | 20 | 20 | 20 | 20 | 20 | | Number of the contacts | 3P+NO | | 3P+NC |
| Type | LC1-D65 | LC1-D80 | LC1-D95 | | Rated operational current (A) | AC-3 | 65 | 80 | 95 | | AC-1 | 28 | 37 | 44 | | AC3-capacity of phase 3 squirrel -cage motor ac3(kw) | 220V/230V | 18.5 | 22 | 25 | | 380V/400V | 30 | 37 | 45 | | 415V | 37 | 45 | 45 | | 440V | 37 | 45 | 45 | | 500V | 37 | 55 | 55 | | 660V/692V | 37 | 45 | 45 | | Rated heat current (A) | 80 | 125 | 125 | | Electrical life | AC4 10 4 | 7-6 | 7-5 | 7-5 | | AC3 10 6 | 1.6 | 1.6 | 1.6 | | Mechanical life 10 6 | 20 | 10 | 10 | | Number of the contacts | 3P+NO | | 3P+NC |
|